Mount the Device
THE LD1500 is a panel mounted device. Use the included wall mount kit and
mount the controller in a convenient location.
Install the Sensing Cable
Leader cable is included with the device and is used to connect sensing cable to
the LD1500, since sensing cable cannot connect directly to the controller.
1. Insert the four stripped wires of the leader cable into the
appropriate slots in the 4-pin terminal block connector -
from left to right: white, black, green, and red. Tighten
the screws on the terminal block connector to secure the
leader cable. Thread the leader cable through a knockout
on the bottom of the enclosure and plug the terminal
block connector into TB2.
2. Unscrew the EOL from the end of the leader cable.
3. Attach the rst length of sensing cable to the leader cable.
4. Route the sensing cable according to your cable layout diagram.
5. Secure the EOL to the unoccupied end of the sensing cable.
Apply Power to the LD1500
A dedicated circuit breaker must be provided within
close proximity to the LD1500 and be clearly marked as
the disconnecting device for the LD1500 leak detection
controller.
RLE recommends using a 24VDC wall adapter power supply (PSWA-DC-24-ST),
which is available separately from RLE.
1. Run a power supply to the location of the unit and plug it into P1. If you’re
© Raymond & Lae Engineering, Inc. 2011. All rights reserved. RLE® is a registered trademark and Seahawk™, Falcon™, and Raptor™ are
trademarks of Raymond & Lae Engineering, Inc. The products sold by Raymond & Lae Engineering, Inc. are subject to the limited warranty, limited
liability, and other terms and conditions of sale set forth at http://rletech.com/RLE-Terms-and-Conditions.html.
Installation Supplies
Included with the LD1500
LD1500 controller
Crossover cable (blue with yellow ends)
15 foot (4.57m) leader cable
End-of-line terminator (EOL)
Available from RLE, Sold Separately
SeaHawk sensing cable - up to 1,500 feet (457m) of conductive uid sensing
cable or 1,050 feet (320m) of chemical sensing cable
Optional Enclosure (LD-ENC)
24VAC power supply (WA-AC-24-ST) or 24VDC power supply (PSWA-DC-24-ST)
Network Communications Information
Consult your IT administrator and determine the following LD1500 network
settings:
IP Address _______________________________________________
Subnet Mask _____________________________________________
Default Gateway __________________________________________
SeaHawk LD1500 Quick Start Guide
Thank you for purchasing a SeaHawk LD1500 distance-read leak detection controller.
This guide outlines basic installation and conguration. Additional support information,
including the LD1500 User Guide, is available on our website - www.rletech.com.
If you need further assistance, please contact RLE Technologies at [email protected]
or call us at 800.518.1519.
v1.0
(05/2013)
Seitenansicht 0
1 2

Inhaltsverzeichnis

Seite 1 - Installation Supplies

Mount the DeviceTHE LD1500 is a panel mounted device. Use the included wall mount kit and mount the controller in a convenient location. Install the

Seite 2 - Test the System

wiring power directly, insert the wires into TB1 as noted.2. Apply power. The device will boot. No alarms should be present. If an alarm is presen

Kommentare zu diesen Handbüchern

Keine Kommentare