SHEET: 16 OF 16
104 Racquette Drive
Fort Collins, CO 80524
(970) 484-6510 Phone
(970) 484-6650 Fax
www.rletech.com
FMS Sensor Wiring Guide
10061_FMS Rev 2.0 (8/13)
FMS Dwyer Temperature/Humidity Falcon Integration
Temperature Setup
Humidity Setup
1. Wire the sensor as shown.
5. Verify the "Calc" Value displays the correct room temperature.
The temperature can also be viewed on the Falcon main page.
SETUP
1. Calculate the Dwyer Output current for temperature.
TROUBLESHOOTING
2. Measure the current flowing into the Falcon Ch- terminal with a
current meter. Verify that it is close to the calculated current
(+/-1%)
3. If measured current current does not match calculated current
then check wiring.
4. Compare the measured current matches the current reading in
the Falcon.
5. Check the wiring if the Falcon current reading does not match
the measured current reading.
6. If the Falcon current reading matches the measured current
and the Falcon calculated value does not match the room
temperature then the offset and gain values are wrong.
Double check the Gain and Offset values.
7. If the temperature displayed in the Falcon is 1 or 2 degrees
above or below the room temperature then adjust the offset by
1 or 2. Do not adjust the gain. Only tweak the offset once the
previous troubleshooting steps have been performed.
8. If the Falcon still does not display the correct temperature
contact RLE Technologies technical support at 970.484.6510.
9. Use similar troubleshooting procedure except use the
following formula to calculate the humidity mA output.
mA =
Room Humidity
100
x 16 + 4
2. Configure the Falcon Input channel (temperature) for "Analog
4-20mA" and enter the gain and offset values. For the -40 -
140F range use Gain 45, Offset -85.
4. Configure the Falcon Input Channel (humidity) for "Analog 4-
20mA" and enter the Gain of 25 and Offset of -25.
4
5
3. For other temperature ranges, use the Calculator function on
the webpage
3
5
2
Example if Room Temp is 70F and your sensor has a range of -40 - 140
( (Actual temp - Sensor Low) / (Sensor High - Sensor Low)) x 16 + 4
( (70 - -40) / (140 - -40)) x 16 + 4 = 13.77
-40 - 140 Degree F Range
P1
VDC
TB 1
VDC
+ -
EXTERNAL
24VDC
+ +
Ch1
+ -
Ch2
+ -
Ch3
+ -
Ch4
+ -
TB 2 Inp ut 1-4
Ch5
+ -
Ch6
+ -
Ch7
+ -
TB 3 Input 5-8
Ch8
+ -
EXTERNAL
GND
- -
TB 4
NC NO C
RELAY 1
NC NO C
RELAY 2
Figure 16.1: Falcon Wiring with the Dwyer
Temperature/Humidity sensor
1