SHEET: 5 OF 16
104 Racquette Drive
Fort Collins, CO 80524
(970) 484-6510 Phone
(970) 484-6650 Fax
www.rletech.com
FMS Sensor Wiring Guide
10061_FMS Rev 2.0 (8/13)
CT120/CT300/CT800/CT2400 FMS Integration
1. Set Input Type to an
Analog 4-20 mA Input.
2. For a 0-100 Amp setting, use
a gain of 25 and an offset of
-25.
3. For other settings, use the
integrated gain/offset
calculator.
FMS Configuration
Figure 5.1: FMS Wiring
Figure 5.2: FMS Input Configuration Interface
P1
VDC
TB1
VDC
+ -
EXTERNAL
24VDC
+ +
Ch1
+ -
Ch2
+ -
Ch3
+ -
Ch4
+ -
TB2 Input 1-4
Ch5
+ -
Ch6
+ -
Ch7
+ -
TB3 Input 5-8
Ch8
+ -
EXTERNAL
GND
- -
TB4
NC NO C
RELAY 1
NC NO C
RELAY 2
+
-
1
2
3
Kommentare zu diesen Handbüchern